Mixing, density and thickness checks

The site checks that show Fendolite-MII has been mixed and applied correctly, with the figures Promat give for each.

A slump test on site: the slumped cone of mix is measured with a tape, next to the scale used for the density check

Mixing

Water, Fendolite-MII15 to 19 litres of clean drinking-quality water per 20 kg bag
Water, Fendolite-TG13 to 17 litres per 20 kg bag
OrderWater first, then add the powder steadily
Mixing time3 minutes

Density and slump

Wet density in the mixer, Fendolite-MII690 to 840 kg/m³
Slump in the mixer, Fendolite-MII40 to 55 mm
Wet density as sprayed, Fendolite-MII1,070 to 1,310 kg/m³
Wet density after mixing, Fendolite-TG900 to 1,200 kg/m³

The checks are made with a one litre cylinder at the start of each shift, after any marked change in temperature, and whenever the mix looks wrong. Use the second mix of the shift, because the first can be affected by cleaning water left in the machine. It helps if the same person does the test each time.

Thickness

  • Measure with a fireproofing thickness gauge at least every 3 metres on each coated face of the flanges and web.
  • Record every reading and work out the average.
  • The specified thickness is a minimum. The recommended tolerance on the average is 0 to +3 mm unless the contract says otherwise.
  • No single coat, of Fendolite-MII or Fendolite-TG, should be less than 8 mm thick.

We supply fire protection depth gauges for this check.

Estimating quantities

As a guide, Promat give a theoretical yield of 62 m² per tonne at 25 mm thick with minimal wastage. Real coverage varies with the applied density, the accuracy of the thickness, solid filling of small sections, the finish and wastage, so allow for that when ordering.

Checking older stock

Bags stored off the ground and under cover keep for the shelf life on the product data sheet. Stock that is older, or has been stored badly, can be checked before use: look for lumps, make a trial mix, check the density and slump, and spray a sample to confirm it adheres.

Quotations

Tell us the quantities and the delivery postcode and we will send a written quotation.