Fire protection is specified on third-party certification. The certificate is the independent assessment of the fire test evidence, and it is the document to ask for.
UL certification
UL 1709 is the rapid rise hydrocarbon fire test used for petrochemical steelwork. UL 263 covers cellulosic building fires. Both products are certified for use in the same list of UL designs, which includes the UL 1709 designs XR719, XR740 and XR750.
How the thickness is set
The certificate lists the designs but not the thicknesses. For steel, the thickness for a given section and fire rating is set out in the UL design, which can be looked up on UL Product iQ.
For concrete, including tunnel linings, Promat calculate the thickness for each project. The calculation takes the fire curve, the duration and the highest temperature allowed at the face of the concrete.
These figures are one example from a Promat calculation and do not replace a calculation for the job. Tell us the structure and the fire rating and we will ask Promat for the thickness.
Fire tests
Promat list fire resistance tests on Fendolite-MII to BS 476 Parts 20 and 21, DIN 4102, ISO 834, ASTM E119, UL 263 and UL 1709. For tunnels it has been tested to the Dutch RWS procedure, the French modified hydrocarbon curve and the Italian UNI 11076. Protected structures can achieve up to 240 minutes of fire resistance.
Reaction to fire
Fendolite-MII is classified A1, non-combustible, to EN 13501-1 in Warringtonfire classification report WF 179083. The classification is based on tests to EN ISO 1182 and EN ISO 1716, and covers wall, ceiling and floor applications over any substrate at any thickness.
CE marking
Fendolite-MII does not carry a CE mark, and Promat have set out why in a technical note.
- A CE mark is only obligatory where a harmonised European standard or European Assessment Document covers the product and requires it. Where none does, the mark must not be applied.
- No harmonised standard or assessment document covers cementitious sprays for hydrocarbon fires. The nearest one works to EN 13501-2, which covers the standard fire curve and slow heating only.
- There is therefore nothing to check conformity against, so the product can be sold and used without a CE mark.
- In oil and gas the UL mark does that job. To carry it, the product has to be tested to UL 1709.
The A1 reaction to fire classification above does not depend on CE marking.
Ask us if you need a copy of the UL certificate, the classification report or the CE marking note.